Type PPC/SC Stage & Lighting Cable 600V

 

Class K stranded (#30) annealed bare copper conductors. A separator tape shall be applied between the conductor and the insulation to facilitate stripping. Black or coloured 105°C flame retardant thermoset elastomer meeting the requirements of UL 1581, Class 47, Table 50.33 and CSA C22.2 No. 96, Table 28. It shall be oil and water resistant and suitable for outdoor use.

Packaging: Long length reels, cut to length.

Applications:

ECS
Catalogue
Number
Conductor AMPS* Insulation Thickness
(inches)
Nominal DCR@20°C
(Ohms/Mft.)
Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
No. AWG
Size
Stranding
WSS06-01 1 6 259 x 30 105 .070 .4056 .345 640
WSS04-01 1 4 413 x 30 140 .070 .2569 .390 928
WSS02-01 1 2 651 x 30 190 .070 .1638 .450 1,214
WSS01-01 1 1 826 x 30 220 .090 .1303 .530 1,635
WSS001-01 1 1/0 1044 x 30 260 .090 .1024 .585 1,922
WSS002-01 1 2/0 1308 x 30 300 .090 .0831 .630 2,385
WSS003-01 1 3/0 1653 x 30 350 .090 .0659 .690 2,822
WSS004-01 1 4/0 2071 x 30 405 .090 .0516 .740 3,494
*Ampacities (Amps per conductor) are based on 30°C ambient temperature in air per the 1999 NEC, Table 400-5(B).

 

Applications:

Stage & Lighting Cables are intended for use indoors and outdoors in motion picture/television studios, carnivals, circuses, fairs, and similar locations in accordance with Articles 520, 525,and 530 of the National Electrical Code.